Setting the Control of the Battery Room Fan
Qualified person
The basic procedure for changing operating parameters is explained in another section ( > Changing Operating Parameters).
Procedure:
- Select Device > Multifunction relay.
- Set the parameter Temp lmt for multifunct. relay with batt comp fan to the battery temperature at which the fan is to be switched on.
- Ensure that the multifunction relay used for control is set to Battery compartment fan or Battery fan in Multicluster ( > Setting the Functions of the Multifunction Relays).
- Ensure that the battery room is sufficiently ventilated in the case of malfunctions – for example, on failure of the multifunction relay.