Connecting the Grounding Conductor


Qualified person

The Sunny Island must be connected via a grounding conductor on the terminal AC1 or AC2 to the ground potential. The conductor cross-section of the grounding conductor must be 10 mm² or larger. If the conductor cross-section is smaller, an additional grounding conductor must connect the Sunny Island with the ground potential.

Additional grounding is fulfilled if the Sunny Island is already grounded due to the grounded battery Connecting the Grounding Conductor with a Grounded Battery).

Cable requirements:

  • Cross-section of the connected line conductor or (maximum 16 mm²)
  • Cable diameters: 7 mm to 14 mm

Procedure:

  1. Push the lever of terminal AC1 Loads/SunnyBoys PE or AC2 Gen/Grid PE upward.
  2. 1426782092
  3. Attach the M25 cable gland to the AC1 or AC2 enclosure opening using the counter nut (torque: 7 Nm).
  4. Strip off 13 mm of the insulation of the grounding conductor.
  5. Lead the cable through the cable gland into the Sunny Island.
  6. Thread the grounding conductor through a ferrite included in the scope of delivery.
  7. Insert the grounding conductor as far as it will go into terminal AC1 Loads/SunnyBoys PE or AC2 Gen/Grid PE and move the lever downward.
  8. Tighten the swivel nut of the cable gland (torque: 2.6 Nm).