Changing the Generator Request via the Charging Process of the Battery


Qualified person

2049639308

The basic procedure for changing operating parameters is explained in another section Changing Operating Parameters).

Procedure:

  1. Select Generator > Generator request via charge type.
  2. Set the parameter Generator request with set charge type to the desired generator request:

Value

Explanation

Equalization charge

Generator request during equalization charge

Full charge

Generator request during full charge

Full and equalization charge

Generator request during equalization and full charge

Off

Deactivation of the generator request via the charging process of the battery