Set battery fallback behavior when energy management is disabled


If SMA energy management is not to be used, SMA recommends making the following settings. If energy management is deactivated and no further settings are made, the battery will behave according to its fallback behavior. The default setting is Values maintained, so that the battery continues to be charged or discharged depending on its last status.

Requirement:

Procedure:

  1. In the focus navigation, select the inverter to which the battery is connected.
  2. Select Configuration > Parameters in the menu.
  3. Set the parameter External active power setting, fallback behavior to Apply fallback values.
  4. Set parameter Fallback of the limitation of the battery discharge. to 0 W.
  5. Set parameter Fallback of the limitation of the battery charge. to 0 W.
  6. Configure the energy management so that the battery should not charge or discharge.
  7. Ensure that the battery is not charging or discharging.
  8. Deactivate the energy management Deactivating the energy management).