Requirements for the PV modules per input


  • All PV modules should be of the same type.

  • All PV modules should be aligned and tilted identically. Otherwise the yields may be reduced.

  • If 2 strings are connected to one input, the same number of PV modules wired in series should be connected to each string. Otherwise the yields may be reduced.

  • On the coldest day based on statistical records, the open-circuit voltage of the PV array must never exceed the maximum input voltage of the inverter.

  • The maximum input current per string must not be exceeded, and must not be greater than the rated through-current of the DC connectors.

  • The thresholds for the input voltage and the input current of the inverter must be adhered to.