Configuring the Digital Input for Fast Stop


Qualified person

Requirements:

  • A switch for a fast stop must be connected to the digital input GSI.

  • The inverter to which the switch is connected, must be configured as System Manager.

  • The user interface must be open and you must be logged in as Installer or Administrator.

Procedure:

  1. Select the product in the focus navigation.
  2. Select the menu Configuration.
  3. Select the menu item I/O configurations.
  4. Select + to add a new configuration.
  5. Select the type of the I/O channel Digital input.
  6. Select the use for the digital input Signal fast stop.
  7. Configure the connected switch as a break contact to ensure the safety of the system in the event of a cable break.
  8. Select the System Manager to which the switch for the fast stop is connected.
  9. Select the digital input.
  10. Assign the name of the I/O channel (e.g. fast stop).
  11. Click on [Save].