Rated Residual Current of the Residual-Current Device
When using residual-current devices with a rated residual current of < 30 mA, set the rated residual current to the respective value in the inverter. In this way the inverter reduces the operational leakage currents and prevents a false triggering of the residual-current device (further information see technical information "Leading Leakage Currents" at www.SMA-Solar.com).
Channel | Name | Settings |
---|---|---|
GridGuard.Cntry.LeakAMax | Disconnection limit for leakage current | Amperage (0.001 A to 0.300 A) |