Requirements for signal cables for backup operation, MFR, and fast stop
The cable length and quality affect the quality of the signal. Observe the following cable requirements:
Conductor type: copper wire
The conductors must be solid or stranded wire.
Maximum cable length within the inverter: 260 mm
Conductor cross-section: 0.2 mm² to 1.5 mm²
External outer diameter: max. 9 mm
Insulation stripping length: 6 mm
Nominal voltage: at least 600 V
Maximum length of conductors: 30 m
The cable type and cable-laying method must be appropriate for the application and location.