Requirements for cables for secure power supply outlets
Conductor type: copper wire
The conductors must be solid or stranded wire.
Conductor cross-section when using solid or stranded wire without bootlace ferrules: 1.5 mm² to 6 mm²
Conductor cross-section when using bootlace ferrules: 1.5 mm² to 4 mm²
External diameter: 10 mm to 14 mm
Insulation stripping length: 10 mm to 12 mm
Maximum length of conductors: 10 m