Setting load management with an external meter
For external metering, the following meters can be used via Modbus TCP:
Manufacturer | Model | Information |
---|---|---|
SMA | SMA COM-EMETER-A-20 / SMA COM-EMETER-B-20 | Select TQ EM300-LR / EM410 or EM420 |
Janitza | UMG 512/96 PRO | Port 502 |
Janitza | UMG 604 PRO | Port 502, as of firmware 5.32, Modbus TCP can also be used for EDMM-10 |
Janitza | UMG 605 PRO | Port 502 |
Phoenix Contact | EEM-MB371/MB370 | Port 502 |
Siemens | 7KM2200 | Port 502, Modbus TCP can also be used for EDMM-10 |
TQ | EM300-LR | Port 502 |
TQ | EM410 / EM420 | Port 502 |
Requirements:
The user interface must be open and you must be logged in.
Procedure:
- In the navigation area, select [Load management].
- Under [Dynamic load management] > Dynamic load management - DLM Master/Slave select [DLM Master (with internal DLM slave)].
Information: The main device (DLM master) may only be configured once. All other charging stations must be configured as a subordinate device (DLM slave)( > Setting the Subordinate Device (Slave) for Load Management). - Under Support for external meters select [On].
- Set the available current on the mains connection under Current limit of the mains connection (L1/L2/L3) [A].
- Set the safety distance to the maximum value under Safety margin for external load (L1/L2/L3) [A].
- Set the assumed load in case of failure under Fallback value of the external load (L1/L2/L3) [A]. If the value 9999 is input, all charging points will be switched off in case of failure.
- Set the type of dynamic load management under Topology of the external meter.
- Under Meter configuration (external meter), select the meter for the external measurement.
- Under IP address of the external meter, set the IP address of the energy meter.
- Under Port number of the external meter, set the port number.
- Click on [Save] to save the changes and [Restart].
- Under [Current status] > [Energy manager] > [External meter] the external meter can be checked.