Setting load management with an external meter


For external metering, the following meters can be used via Modbus TCP:

Manufacturer

Model

Information

SMA

SMA COM-EMETER-A-20 / SMA COM-EMETER-B-20

Select TQ EM300-LR / EM410 or EM420

Janitza

UMG 512/96 PRO

Port 502

Janitza

UMG 604 PRO

Port 502, as of firmware 5.32, Modbus TCP can also be used for EDMM-10

Janitza

UMG 605 PRO

Port 502

Phoenix Contact

EEM-MB371/MB370

Port 502

Siemens

7KM2200

Port 502, Modbus TCP can also be used for EDMM-10

TQ

EM300-LR

Port 502

TQ

EM410 / EM420

Port 502

Requirements:

  • The user interface must be open and you must be logged in.

Procedure:

  1. In the navigation area, select [Load management].
  2. Under [Dynamic load management] > Dynamic load management - DLM Master/Slave select [DLM Master (with internal DLM slave)].
    Information: The main device (DLM master) may only be configured once. All other charging stations must be configured as a subordinate device (DLM slave)Setting the Subordinate Device (Slave) for Load Management).
  3. Under Support for external meters select [On].
  4. Set the available current on the mains connection under Current limit of the mains connection (L1/L2/L3) [A].
  5. Set the safety distance to the maximum value under Safety margin for external load (L1/L2/L3) [A].
  6. Set the assumed load in case of failure under Fallback value of the external load (L1/L2/L3) [A]. If the value 9999 is input, all charging points will be switched off in case of failure.
  7. Set the type of dynamic load management under Topology of the external meter.
  8. Under Meter configuration (external meter), select the meter for the external measurement.
  9. Under IP address of the external meter, set the IP address of the energy meter.
  10. Under Port number of the external meter, set the port number.
  11. Click on [Save] to save the changes and [Restart].
  12. Under [Current status] > [Energy manager] > [External meter] the external meter can be checked.