Setting Time-Based Charging
If you activate time-based charging, dynamic load management will not exceed the limit value configured in the schedules. Each entry specifies the maximum permitted current for each phase from the time entered. Each entry is valid until it is replaced by another suitable entry.
Information: All time information uses the UTC time zone.
Example: In the first entry, enter hour 5. Enter 10 A for each of L1, L2 and L3. Then add another entry. Enter 10 under hour. Enter 20 A for each of L1, L2 and L3. In the example, the two entries would use 10 A as the maximum value from 5:00 a.m. UTC to 9:59:59 a.m. UTC. At 10:00 UTC, the maximum would be set to 20 A and would be valid until 4:59:59 UTC the next day.
Requirements:
The user interface must be open and you must be logged in.
Procedure:
- In the navigation area, select [Load management].
- Under DLM Charging current schedule > Schedule for maximum charging current, change the value to [On].
- A section opens below to add entries.
- Select [Add entry] and enter values.
- Click on [Save] to save the changes and [Restart].