Setting load management without external meters


Requirements:

  • The user interface must be open and you must be logged in.

Procedure:

  1. In the navigation area, select [Load management].
  2. Under [Dynamic load management] > Dynamic load management - DLM Master/Slave select [DLM Master (with internal DLM slave)].
  3. Under Support for external meters select [Off].
  4. Set the available current on the mains connection under Current limit of the mains connection (L1/L2/L3) [A].
  5. Set the safety distance to the maximum value under Safety margin for external load (L1/L2/L3) [A].
  6. Set the assumed load in case of failure under Fallback value of the external load (L1/L2/L3) [A]. If the value 9999 is input, all charging points will be switched off in case of failure.
  7. Set the type of dynamic load management under Topology of the external meter.
  8. Click on [Save] to save the changes and [Restart].