Setting load management without external meters
Requirements:
The user interface must be open and you must be logged in.
Procedure:
- In the navigation area, select [Load management].
- Under [Dynamic load management] > Dynamic load management - DLM Master/Slave select [DLM Master (with internal DLM slave)].
- Under Support for external meters select [Off].
- Set the available current on the mains connection under Current limit of the mains connection (L1/L2/L3) [A].
- Set the safety distance to the maximum value under Safety margin for external load (L1/L2/L3) [A].
- Set the assumed load in case of failure under Fallback value of the external load (L1/L2/L3) [A]. If the value 9999 is input, all charging points will be switched off in case of failure.
- Set the type of dynamic load management under Topology of the external meter.
- Click on [Save] to save the changes and [Restart].