Setting Power Reduction in Accordance With the Requirements of EnWG §14a
Requirements:
The user interface must be open and you must be logged in.
Procedure:
- In the navigation area, select [Load management].
- Under [DLM External measurement and control] > Status of external input 1, change the value to ['Use Opto 1 In'].
- The parameters Polarity of external input 1 and Current offset (L1/L2/L3) [A] of external input 1 become visible.
- Select [High-active] under Polarity of external input 1.
- Under Current offset (L1/L2/L3) [A] of external input 1, ensure that all values are set to [0].
- Click on [Save] to save the changes and [Restart].