Setting Power Reduction in Accordance With the Requirements of EnWG §14a


Requirements:

  • The user interface must be open and you must be logged in.

Procedure:

  1. In the navigation area, select [Load management].
  2. Under [DLM External measurement and control] > Status of external input 1, change the value to ['Use Opto 1 In'].
  3. The parameters Polarity of external input 1 and Current offset (L1/L2/L3) [A] of external input 1 become visible.
  4. Select [High-active] under Polarity of external input 1.
  5. Under Current offset (L1/L2/L3) [A] of external input 1, ensure that all values are set to [0].
  6. Click on [Save] to save the changes and [Restart].