Connecting the Digital Input
Qualified person
- Connect the connection cable to the ripple control receiver or the remote terminal unit (see the manual from manufacturer).
- Disconnect the inverter from voltage sources and secure it against being switched on again ( > Disconnecting the Inverter from Voltage Sources).
- When using a self-assembly network cable, assemble the RJ45 connectors and connect them to the network cable (see connector documentation).
- Remove the cover from the communication connection area.
- Remove the swivel nut from one of the cable glands for the communication cable.
- Thread the swivel nut over the network cable.
- Remove the two-hole cable support sleeve from the cable gland. As required, use the cable support sleeve for a cable diameter of between 4.5 mm to 6 mm or between 6 mm to 8 mm that is included in the scope of delivery.
- Remove the sealing plug from one of the enclosure openings of the two-hole cable support sleeve and insert the cable into the enclosure opening. Ensure that the cable is located about 15 cm within the cover so as not to damage the connector when pulling off the cover.
- Strip off a maximum of 6 mm of the cable insulation.
- Unlock the conductor inserts on the provided 6-pole connector by loosening the screw.
- Connect the conductors of the connection cable to the supplied 6-pole connector. To do so, plug the conductors into the conductor entries and close the conductor entries by tightening the screws. Observe the connector assignment.
- Plug the 6-pole connector into the port DI: D1-D4, Vcc on the product. Observe the pin assignment.
- Ensure that the connector is securely in place.
- Ensure that all conductors are correctly connected.
- Ensure that the conductors sit securely in the terminal points.
- Tighten the swivel nut on the cable gland hand-tight.