Residual-current monitoring unit
The inverter does not require an external residual-current device when operating. If local regulations require the use of a residual-current device, the following must be observed:
The inverter is compatible with type B residual-current devices with a rated residual current of 1250 mA or higher (see Technical Information "Criteria for Selecting a Residual-Current Device" in www.SMA-Solar.com for information on how to select a residual-current device). Each inverter in the system must be connected to the utility grid via a separate residual-current device.
When using residual-current devices with a lower rated residual current, there is a risk of false tripping of the residual-current device, depending on the system design.