Connecting contact for fast stop


  1. Connect the connection cable to the switch for the fast stop (see the manual from manufacturer).
  2. Disconnect the inverter from voltage sources and secure it against being switched on again ( > Disconnecting the Inverter from Voltage Sources).
  3. Connect the connection cable to the 2-pole connector (included in the scope of delivery).
  4. 17253771404

  5. Plug the 2-pole connector into the socket on the communication assembly. Observe the pin assignment.
  6. Ensure that the connector is securely in place.
  7. Ensure that all conductors are correctly connected.
  8. Ensure that the conductors are plugged into the terminal points.
  9. Close and commission the inverter (see inverter manual).