Event 5019


Qualified person

Event message:

  • Isolator Not Closed

Explanation:

Insulator not closed.
The circuit breaker has tripped or the high voltage measurement line is loose. This message can also be issued as a result of other events (e.g. 5039 or 5042) for which the protective measure is to trip the circuit breaker.

Corrective measures:

  • Close the circuit breaker.

  • Check the B+ measurement line in the main distribution box.

  • Restart the battery.