Event E128


Qualified person

Event message:

  • Control Failure in Battery Pack #X Contactor

Explanation:

During the control of the switching operation (Close/Open), the system did not receive the correct status feedback signal from the main contactor or pre-charge contactor of battery module X# within the specified time, resulting in a failure of the control process. The system subsequently entered an error state.

Corrective measures:

  • First, execute a stop command via the system interface to ensure that the module affected and the entire system are in a safe state.

  • Control circuit check: Measure the voltage at the contactor coil and check the control relay and the cabling.

  • Feedback circuit check: Ensure that the auxiliary contact used for status feedback and the corresponding cabling are functioning correctly.

  • Repair the cabling or replace the defective contactor / feedback part. After the repair, try to actuate the contactor from the system again to ensure that both its function and the feedback signal are back to normal.

  • The error will be automatically reset as soon as the contactor has performed a correct action successfully.