Event 5039


Qualified person

Event message:

  • Isolating switch tripping

Explanation:

Circuit breaker tripped.
Temperature above 75°C at an electrical current of 2 A or maximum cell voltage above the threshold. If alternating current is present after tripping, this can lead to further events (5019, 5020 or 5029).

Corrective measures:

  • Upon checking, switch the miniature circuit breaker back on.

  • Restart the battery.