AC grid connection
STP5.0-3SE-40 | STP6.0-3SE-40 | STP8.0-3SE-40 | STP10.0-3SE-40 | |
|---|---|---|---|---|
Rated power at 230 V, 50 Hz | 5000 W | 6000 W | 8000 W | 10000 W |
Maximum apparent power at cos φ = 1 | 5000 VA | 6000 VA | 8000 VA | 10000 VA |
Rated apparent power at cos φ = 1 | 5000 VA | 6000 VA | 8000 VA | 10000 VA |
Nominal grid voltage | 3/N/grounding conductor; 220 V / 380 V 3/N/grounding conductor; 230 V / 400 V 3/N/grounding conductor; 240 V / 415 V | 3/N/grounding conductor; 220 V / 380 V 3/N/grounding conductor; 230 V / 400 V 3/N/grounding conductor; 240 V / 415 V | 3/N/grounding conductor; 220 V / 380 V 3/N/grounding conductor; 230 V / 400 V 3/N/grounding conductor; 240 V / 415 V | 3/N/grounding conductor; 220 V / 380 V 3/N/grounding conductor; 230 V / 400 V 3/N/grounding conductor; 240 V / 415 V |
Rated grid voltage | 230 V | 230 V | 230 V | 230 V |
Voltage range | 156 V to 277 V | 156 V to 277 V | 156 V to 277 V | 156 V to 277 V |
Rated current at 230 V | 3 x 7.3 A | 3 x 8.7 A | 3 x 11.6 A | 3 x 14.5 A |
Maximum output current | 3 x 7.6 A | 3 x 9.1 A | 3 x 12.1 A | 3 x 15.2 A |
Maximum input power for backup loads in parallel grid operation | 13800 W | 13800 W | 13800 W | 13800 W |
Maximum input current for backup loads in parallel grid operation | 3 x 20 A | 3 x 20 A | 3 x 20 A | 3 x 20 A |
Rated grid frequency | 50 Hz | 50 Hz | 50 Hz | 50 Hz |
Operating range at grid frequency 50 Hz | 45 Hz to 55 Hz | 45 Hz to 55 Hz | 45 Hz to 55 Hz | 45 Hz to 55 Hz |
Power factor at rated power | 1 | 1 | 1 | 1 |
Displacement power factor cos φ, adjustable | 0.8 overexcited to 0.8 underexcited | 0.8 overexcited to 0.8 underexcited | 0.8 overexcited to 0.8 underexcited | 0.8 overexcited to 0.8 underexcited |
Feed-in phases | 3 | 3 | 3 | 3 |
Connection phases | 3 | 3 | 3 | 3 |
Grid configurations | TN-C, TN-S, | TN-C, TN-S, | TN-C, TN-S, | TN-C, TN-S, |
Overvoltage category as per IEC 60664-1 | III | III | III | III |