Event 4014
 Qualified person
Qualified person
Event message:
- Reverse currents or input X polarity reversed 
- Check generator 
Explanation:
The displayed input is in reverse polarity or reverse current has been detected in the input.
Corrective measures:
- Check the correct polarity of the connected PV modules. 
- Ensure correct design and circuitry of the PV array. 
- If solar irradiation is sufficient, check whether the same voltage is present at the DC inputs. 
- Ensure that no PV module is defective.