Check the PV system for ground faults by measuring the voltage


Qualified person

Proceed as follows to check each string in the PV system for ground faults.

Procedure:

  1. DANGER

    Danger to life due to high voltages

    1. Disconnect the inverter from all voltage sources.
  2. Measure the voltage between the positive terminal and the ground potential (PE).
  3. Measure the voltage between the negative terminal and the ground potential (PE).
  4. Measure the voltage between the positive and negative terminals.
  5. If the following results are present at the same time, there is a ground fault in the PV system:
  6. All measured voltages are stable.
  7. The sum of the two voltages to ground potential is approximately equal to the voltage between the positive and negative terminals.
  8. If a ground fault is present, determine the location of the ground fault via the ratio of the two measured voltages and eliminate the ground fault.
  9. If a definite ground fault cannot be measured and the message is still displayed, measure the insulation resistance
  10. Reconnect the strings without ground faults to the inverter and recommission the inverter (see inverter installation inverter).

Location of the ground fault

The example shows a ground fault between the second and third PV module.

14271251724