DC Connection for Battery


SI4.4M-13

SI6.0H-13

SI8.0H-13

Rated input voltage

48 V

48 V

48 V

Voltage range

41 V to 63 V

41 V to 63 V

41 V to 63 V

Rated charging current

63 A

90 A

115 A

Rated discharging current

75 A

103 A

136 A

Maximum battery charging current

75 A

110 A

140 A

Battery type

Lead-acid battery: FLA, VRLA lithium-ion battery 1)

Lead-acid battery: FLA, VRLA lithium-ion battery 1)

Lead-acid battery: FLA, VRLA lithium-ion battery 1)

Battery capacity range of lead-acid batteries

100 Ah to 10000 Ah

100 Ah to 10000 Ah

100 Ah to 10000 Ah

Battery capacity range of lithium-ion batteries

50 Ah to
10000 Ah

50 Ah to
10000 Ah

50 Ah to
10000 Ah

Recommended minimum battery capacity C10 in systems for increased self-consumption

100 Ah

100 Ah

100 Ah

Recommended minimum battery capacity C10 in battery-backup systems

100 Ah

120 Ah

160 Ah

Recommended minimum battery capacity C10 in off-grid systems

150 Ah

190 Ah

250 Ah

Minimum capacity recommended for lead-acid batteries C10 per 1000 Wp output of the PV system in off-grid systems

100 Ah

100 Ah

100 Ah

Minimum capacity recommended for lithium-ion batteries C10 per 1000 Wp output of the PV system in off-grid systems

50 Ah

50 Ah

50 Ah

Charge control for lead-acid batteries

IUoU charging behavior with automatic full charge and equalization charge

IUoU charging behavior with automatic full charge and equalization charge

IUoU charging behavior with automatic full charge and equalization charge

DC connection

Terminal lug M8, 20 mm to 25 mm wide

Terminal lug M8, 20 mm to 25 mm wide

Terminal lug M8, 20 mm to 25 mm wide

Permitted conductor cross-section:

50 mm² to
95 mm²2)

50 mm² to
95 mm²2)

50 mm² to
95 mm²2)

Maximum connectable conductor cross-section

95 mm²2)

95 mm²2)

95 mm²2)

Cable diameter

14 mm to 25 mm

14 mm to 25 mm

14 mm to 25 mm

Torque

12 Nm

12 Nm

12 Nm

1) The lithium-ion battery must be approved for use with the Sunny Island (see technical information at “List of Approved Batteries”).

2) In the event of a cross-section of 95 mm², observe the maximum cable diameter.