Connecting ExtVtg


Qualified person

Always connect the cable to the ExtVtg connection as follows.

Additionally required material (not included in the scope of delivery):

  • Suitable bootlace ferrules if using stranded wire

Cable requirements:

  • Copper wire
  • Conductor cross-section: 0.2 mm² to 2.5 mm²
  • The cable length must be less than 3 m.

Procedure:

    1426899724
  1. On the Sunny Island, attach the M20 cable gland to the PE/ExtVtg enclosure opening with the counter nut (torque: 5 Nm).
  2. Strip 7 mm of the cable insulation.
  3. Lead the cable through the cable gland into the Sunny Island.
  4. Connect the insulated conductors to the 2-pole terminal blocks included in the scope of delivery (torque: 0.5 Nm to 0.6 Nm, blade width: 1 mm):
    • Connect the line conductor to terminal ExtVtg L.

    • Connect the neutral conductor to terminal ExtVtg N.

  5. Ensure that the conductors are plugged completely into the terminals up to the insulation.
  6. In accordance with the labelling, plug the 2-pole terminal block into the connection ExtVtg on the inverter until the terminal block audibly snaps into place.
  7. Ensure that the seal insert is positioned correctly in the cable gland.
  8. Tighten the swivel nut of the cable gland (torque: 2.6 Nm).