Connecting the Control Cable of the Multicluster-Box 12
Qualified person
Requirement:
-
The inverters to be connected must be Sunny Island 6.0H / 8.0H inverters.
Procedure:
- On the master of the main cluster, connect the X106 1 line conductor and X106 2 neutral conductor (for the control voltage) to terminal AC1 Loads/SunnyBoys ( > Connecting the AC Power Cable).
- When making the following connections, always insert a silicone tube ( > Connecting Relay 1 and Relay 2).
- On the master of the main cluster, connect the control cable of X113 1 and X113 2 to the Relay2 C and Relay2 NO ( > Connecting Relay 1 and Relay 2).
- On the main cluster's master, connect the control cable of X112 1 and X112 2 to the Relay1 C and Relay1 NC terminals when a Grid-Connect-Box is installed in addition to the Multicluster-Box 12.
WARNING
Danger to life from electric shock due to incorrect insulation
In the case of faulty insulation, supposedly de-energized parts or cables may be live. Touching live components or cables can result in death or serious injury due to electric shock.