Checking the Function
Testing period
For new systems, check every week during the 6 months following commissioning whether error messages have been logged. This will reveal any hidden errors in the installation or configuration.
For all other systems, check every 6 months whether error messages have been logged.
Procedure:
- Activate the user interface of the inverter ( > Establishing a connection to the user interface).
- Log in as User ( > Logging In and Out of the User Interface).
- Select the menu Events.
- Set filter. Activate Warning and Error. Deactivate Information.
- Set the desired time period and select [Apply time filter].
- If error messages have been logged, eliminate the cause ( > Event messages).