Connecting the Utility Grid in the System for Increased Self-Consumption
Qualified person

Requirements:
The system may not be a battery-backup system or an off-grid system.
For connection of the Sunny Island inverter to the utility grid, there must be a circuit breaker and a type A residual-current device on the distribution board (see circuitry overview in the quick reference guide "SMA Energy System Home")
Procedure:
- On the Sunny Island, connect the power cable to the AC2 Gen/Grid. When doing so, connect the line conductor to AC2 Gen/Grid L and the neutral conductor to AC2 Gen/Grid NTT( > Connecting the AC Power Cable).
- Thread the grounding conductor through a ferrite included in the scope of delivery and connect to AC2 Gen/Grid PE ( > Connecting the Grounding Conductor).
- If the power cable conductor cross-section is less than 10 mm², thread an additional grounding conductor through the provided ferrite and connect it to the AC1 Loads/SunnyBoys PE terminal ( > Connecting the Grounding Conductor).