Configure additional direct seller's specifications for the country data set.
Qualified person
During device registration, the required country data sets are selected for the detected devices. To achieve the correct control speed for the country data set, you need to make additional settings.
These settings refer to the PT1 element and the gradient to compensate for jumps in the incoming active power setpoints. These settings are configured separately for grid operators and direct sellers. By default, the value 3 s is set for the PT1 element and 0.5 %/s is set for the gradient. These values need to be adjusted according to the requirements of the grid operator.
Requirements:
The user interface must be open and you must be logged in as Installer or Administrator.
Procedure:
- Select the system in the focus navigation.
- Select the menu item Grid management service in the menu Configuration.
- Select the button Configuration & activation in the Active and reactive power row.
- Open the configuration wizard for Direct seller settings under Active power.
- Under the Direct seller settings, activate the Source for external setpoint and select one of the available options.
- Activate Behavior in case of setpoint change.
- Select Implementation with PT1 element and enter the values provided by the grid operator in the field Setting time. To achieve the fastest control speed, deactivate this option.
- Select Gradient and enter the values provided by the grid operator for Max. increase of the default value and Max. decrease of the default value. To achieve the fastest control speed, deactivate this option.
- Click on [Next].
- Click on [Save].
- Select the device in the focus navigation and make the same settings as at system level.