Separated reference values for the active power limitation


The total AC power that the grid management service settings refer to is the sum of the outputs of PV, hybrid and battery inverters. Without any further configuration, external setpoints for active power limitation of direct sellers or grid providers are given as a percentage of the total AC power. If the active power limitation is to refer to other reference values, configurations must be made in the parameters at the system level.

While the parameters can be used independently, they are recommended for direct sellers and grid providers due to differing setpoint priorities: the grid operator’s setpoints take precedence over those of the direct seller.

Channel

Name

Settings

Inverter.WModCfg.WCtlComCfg.WRefMod

External active power setpoint, selection of reference value

Maximum active power VMax: Default setting

Reference value Active power: This setting enables modification of the reference value used for direct sellers

Inverter.WModCfg.WCtlComCfg2.WRefMod

External active power setpoint2, selection of reference value

Maximum active power VMax: Default setting

Reference value Active power: This setting enables modification of the reference value used for grid providers

Inverter.WModCfg.WCtlComCfg.WSptRef

External active power specification, reference value

Individual reference value in W for direct sellers

Inverter.WModCfg.WCtlComCfg2.WSptRef

External active power specification 2, reference value

Individual reference value in W for grid providers