Setting Zero Export


Qualified person

To set the zero feed-in, the corresponding parameters must be set in the connected inverters and the system.

Requirements:

  • The user interface must be open and you must be logged in as Installer or Administrator.

  • The parameter External active power setting, limitation of change rate must be disabled in the inverter.

  • The parameter External active power setting 2, limitation of change rate must be disabled in the inverter.

  • The parameter External active power setting, nominal value filter must be disabled in the inverter.

  • The parameter External active power setting 2, nominal value filter must be disabled in the inverter.

Procedure:

  1. Select the system in the focus navigation.
  2. Select the menu Configuration.
  3. Select the Parameters menu item.
  4. Select the value On for the parameter Activation of plant control based on maximum of active power phase measured value.
  5. Click on [Save].