Signal cable requirements for temperature input X8


  • Conductor cross-section: 0.5 mm² (21 AWG) to 1.5 mm² (16 AWG)

  • Maximum cable length with 4-conductor measurement: < 30 m (98 ft)

  • Maximum cable length with 2-conductor measurement: < 2.5 m (8 ft)

  • Twisted pair conductors

  • Cable with shielding: Yes (on one side on external shield connection terminal)