Network cable requirements X14 to X16
The cable length and quality affect the quality of the signal. Observe the following cable requirements:
Cable type: 100BaseTx
Cable category: minimum CAT5e
Plug type: RJ45 of Cat5, Cat5e, Cat6 or Cat6a (Cat7 plugs cannot be used)
Shielding: S/UTP, F/UTP or higher
Number of insulated conductor pairs and insulated conductor cross-section: at least 2 x 2 x 0.22 mm² (2 x 2 x 24 AWG)
Maximum cable length between two nodes when using patch cables: < 50 m (164 ft)
Maximum cable length between two nodes when using installation cables: < 100 m (328 ft)
UV-resistant for outdoor use