Connect switch for fast stop to X2
Qualified person
Requirements:
The signal source must be technically suitable for connection to the digital inputs ( > Technical Data).
The connected digital signal source has a safe separation to the grid potential. When connecting the digital signal source the potential-free contact or an external potential-free contact is used.
The connection cable is prepared for connection to the multipole connector ( > Preparing the Connection Cable).
Procedure:
- Connect the connection cable to the switch for the fast stop (see the manual from manufacturer).
- Connect the connection cable to the supplied two-pole plug. Ensure that the conductors are plugged completely into the terminal points up to their insulation.
- Plug the 2-pole connector into the socket X2 on the product. Observe the pin assignment.
- Ensure that the connector is securely in place.
- Ensure that all conductors are correctly connected.
- Ensure that the conductors sit securely in the terminal points.