Configuring Sunny Tripower CORE2


The Data Manager can control the inverter Sunny Tripower CORE2 (STP 110-60). The Modbus TCP protocol is used here in accordance with information model 123 of the SunSpec Modbus standard. This allows the operation of active power and reactive power with control intervals of 1000 ms.

Requirements:

  • All devices in the local network must be in operation and connected to the product via an Internet router.

  • The inverters must have the current firmware version in each case (see the inverter product page of the PV inverter at www.SMA-Solar.com).

  • The country data set each valid must be set.

Procedure:

  1. Log into the user interface of the Data Manager.
  2. On the system level in the Configuration menu, select the Parameters menu item and for the parameter Call interval for the control at the system level the value 1.0.
  3. Select the menu item Device administration in the menu Configuration.
  4. In the row of the required inverter, select the button.
  5. Select [Display parameters].
  6. For the parameter ActPowSpeedEna set the value 100.