Bring the battery modules to a state of charge of 30%

Exception for battery systems with STPx.0-3SE-40
Battery systems with STPx.0-3SE-40 require at least 2 operational battery modules for commissioning. Only for battery systems with STPx.0-3SE-40, the following measure applies:
- If, after disassembling the defective battery modules, only one battery module remains in the battery system, continue directly with assembling and connecting the new battery module.
Requirement:
Removing the defective battery module is complete.
Procedure:
- Recommission the system with the remaining battery modules.
- Bring all remaining battery modules to a state of charge of 30%. To do this, determine the current state of charge via the user interface of the inverter and charge or discharge the battery depending on the current state of charge.
- Disconnect the battery modules from voltage sources again ( > Disconnecting the battery modules from voltage sources).