Battery Management


10147051276

State of charge ranges of the battery

Range

Inverter parameters

Inverter behavior

A

-

The inverter uses the battery within this range for increased self-consumption. When more energy is needed than can be supplied by the PV modules, the battery is discharged.

B

Battery > Areas of application > Minimum width of backup power area (BatUsDm.BckDmMin)

The value indicates the percentage of battery charge to be retained for battery-backup operation. This battery charge cannot be used in parallel grid operation, even if the battery-backup operation is deactivated.

C

Device > Self-consumption > Lower battery discharge limit (BatChaSttMin)

In this range, the battery is no longer discharged, even in battery-backup operation.

D

Battery > Areas of application > Minimum width of deep discharge protection area (BatUsDm.DschProDmMin)

The value specifies which percentage of the Real SOC is to be reserved as deep discharge protection. This value corresponds to a User SOC of 0%. When the state of charge is displayed as 0% (User SOC), the battery is actually (Real SOC) still charged to as much percentage as this value indicates.