Connecting the DC Cables


Qualified person

To connect the DC cables, always connect the 2 nearest battery modules to each other. All battery modules are connected in series.

Additionally required material (not included in the scope of delivery):

  • 2 DC cables for connecting to the inverter

  • At least 1 longer DC cable is required to connect the battery modules to each other if they are not mounted directly above each other. This is unavoidable for:

    • 4 or 5 battery modules

    • Back-to-back

Requirement:

  • The battery modules must be mounted.

  • All grounding cables must be connected.

Procedure:

  1. Ensure that the battery modules and the inverter are disconnected from all voltage sources.
  2. To make a longer cable, use the provided MC4 connectors.
  3. 12577953292
  4. Connect the battery modules to each other in series. For this, connect the plug connector of the DC cable BAT+ with the BAT- connector.
  5. Prepare the DC cables of the inverter. If needed, crimp the provided MC4 connectors with the cables.
  6. 13010323212
  7. Connect the top plug connector BAT+ of the top or last battery module with the positive terminal of the inverter (see inverter documentation). Pay attention to the polarity details on the battery module and inverter.
  8. 13010323596
  9. Connect the bottom plug connector BAT- of the bottom or first battery module with the negative terminal of the inverter (see inverter documentation). Pay attention to the polarity details on the battery module and inverter.

    Also see: