Connecting the DC Cables
Qualified person
To connect the DC cables, always connect the 2 nearest battery modules to each other. All battery modules are connected in series.
Additionally required material (not included in the scope of delivery):
2 DC cables for connecting to the inverter
At least 1 longer DC cable is required to connect the battery modules to each other if they are not mounted directly above each other. This is unavoidable for:
4 or 5 battery modules
Back-to-back
Requirement:
The battery modules must be mounted.
All grounding cables must be connected.
Procedure:
- Ensure that the battery modules and the inverter are disconnected from all voltage sources.
- To make a longer cable, use the provided MC4 connectors.
- Connect the battery modules to each other in series. For this, connect the plug connector of the DC cable BAT+ with the BAT- connector.
- Prepare the DC cables of the inverter. If needed, crimp the provided MC4 connectors with the cables.
- Connect the top plug connector BAT+ of the top or last battery module with the positive terminal of the inverter (see inverter documentation). Pay attention to the polarity details on the battery module and inverter.
- Connect the bottom plug connector BAT- of the bottom or first battery module with the negative terminal of the inverter (see inverter documentation). Pay attention to the polarity details on the battery module and inverter.