Event 5160 / A0 / 9347
Qualified person
Event number:
Firmware version | Event number |
---|---|
< 3.4.20.R | 9347 |
3.4.20.R | A0 Example: 0x01A0, 0x0001, 0x0000, 0x0000 Number of the battery module: 01 |
≥ 3.5.x.R | 5160 or 160 |
Event message:
Battery is reporting event: 0x0XA0, 0x0001, 0x0000, 0x0000
Explanation:
The firmware versions are not consistent.
LED signal on battery module:
Red LED is flashing slowly.
Corrective measures:
Connect each battery module to the inverter individually.
Check for each individual battery module whether the current firmware version is installed.
If the current firmware version is not installed for a battery module, perform a firmware update for this battery module. To do this, commission the inverter (see inverter manual). The firmware update of the battery module automatically starts approx. ten minutes after recommissioning the inverter.