Event 5168 / A8 / 9347
Qualified person
Event number:
Firmware version | Event number |
---|---|
< 3.4.20.R | 9347 |
3.4.20.R | A8 Example: 0x01A8, 0x0001, 0x0000, 0x0000 Number of the battery module: 01 |
≥ 3.5.x.R | 5168 or 168 |
Event message:
Battery is reporting event: 0x0XA8, 0x0001, 0x0000, 0x0000
Explanation:
The battery voltage is too low during the precharge phase.
LED signal on battery module:
Red LED is glowing continuously.
Corrective measures:
Switch off the DC circuit-breaker on the battery module.
Stop and then restart the inverter.
Wait a few seconds.
Switch on the DC circuit-breaker on the battery module.
If the error persists, contact Service.