Error Messages
During operation of the PV system, events may occur which can refer to one or several inverters or the Sunny Multigate. Events can be information, warnings or errors. All events are displayed in the communication product you are using (e.g. Sunny Portal, Sunny Explorer). Sunny Explorer additionally displays the corresponding event number for each event.
Inverter
Event number |
Event, cause and corrective measures |
---|---|
102 |
Grid fault / Grid overvoltage fast (102) The grid voltage or grid impedance at the connection point of the inverter is too high. The inverter has disconnected from the utility grid. Corrective measures:
|
202 |
Grid fault / Grid undervoltage fast (202) The utility grid has been disconnected, the AC cable is damaged or the grid voltage at the connection point of the inverter is too low. The inverter has disconnected from the utility grid. Corrective measures:
If the grid voltage is outside the permissible range due to local grid conditions, contact the grid operator. The grid operator must approve changes to the operating parameters of the inverter. If the grid voltage is permanently within the permissible range and this message is still displayed, contact the SMA Service Line. |
301 |
Grid fault / Voltage increase protection (301) The grid voltage or grid impedance at the connection point is too high. The inverter disconnects from the utility grid to comply with the power quality. Corrective measures:
|
401 |
Grid fault / Island grid (401) The inverter is no longer in grid parallel operation and has stopped feed-in operation for safety reasons. Corrective measures:
|
501 |
Grid fault / Grid frequency disturbance (501) The power frequency is not within the permissible range. The inverter has disconnected from the utility grid. Corrective measures:
|
3401 |
DC overvoltage / Overvoltage input A (SW) (3401) The DC input voltage connected to the inverter is too high. This can destroy the inverter. Corrective measures:
If the DC voltage is below the maximum input voltage of the inverter, reconnect the DC connectors to the inverter. If the DC voltage is above the maximum input voltage of the inverter, ensure that the PV array has been correctly rated or contact the installer of the PV array. If this message is repeated frequently, contact the SMA Service Line. |
3501 |
Insulation resistance / Insulation failure (3501) The inverter has detected a ground fault in the PV array. As long as the fault exists, the inverter will not feed in. Corrective measures:
|
3902 |
Waiting for DC start conditions / Generator voltage too low / Start conditions not met (3902) The PV array voltage is too low. Corrective measures:
|
3903 |
Waiting for DC start conditions / Generator voltage too high / Start conditions not met (3903) The PV array voltage is too high. Corrective measures:
|
6002 … 6006 |
Self diagnosis > Interference of device (6002, 6005, 6006) The cause must be determined by the SMA Service Line. Corrective measures:
|
6305 |
Self diagnosis > Interference of device (6305) The cause must be determined by the SMA Service Line. Corrective measures:
|
6402 |
Self diagnosis / Overtemperature (6402) The cause must be determined by the SMA Service Line. Corrective measures:
|
6406 |
DC overcurrent / Overcurrent input A (HW) (6406) The current at the module input of the inverter is too high. The inverter has interrupted the feed-in operation. Corrective measures:
|
6415 |
Self diagnosis > Interference of device (6305) The cause must be determined by the SMA Service Line. Corrective measures:
|
6450 |
Self diagnosis / Energy transfer not possible / Interference device (6450) The inverter cannot feed into the utility grid. Possible causes: grid voltage is too high; a PV module is defective, soiled or shaded; a cloudy or foggy day. Corrective measures:
If the grid voltage is outside the permissible range due to local grid conditions, contact the grid operator. The grid operator must approve changes to the operating parameters of the inverter. Clean the PV module if soiled. |
10265 |
PLC communication impaired (10265) The cause must be determined by the SMA Service Line. Corrective measures:
|
Sunny Multigate
Event number |
Event, cause and corrective measures |
---|---|
6702 |
Interference device (6702) The cause must be determined by the SMA Service Line. Corrective measures:
|
7001 |
Fault sensor interior temperature (7001) The temperature sensor for the indoor temperature of the Sunny Multigate is defective. Feed-in operation will be interrupted. Corrective measures:
|
8101 … 8102 |
Communication disturbed (8101, 8102) An error has occurred in the internal communication. This can be caused by one of the following: Feed-in operation continues. Corrective measures:
|
8104 |
Interference device (8104) The cause must be determined by the SMA Service Line. Corrective measures:
|
9014 |
Invalid device combination (9014) The Sunny Multigate and the inverters cannot be operated in this combination. Corrective measures:
|
9015 |
Max. permitted number of inverters exceeded (9015) The number of inverters connected exceeds the maximum number specified in the currently set standard. Corrective measures:
|
10221 |
New device cannot be administered (10221) The cause must be determined by the SMA Service Line. Corrective measures:
|
10259 |
Inconsistent communication version (10259) The communication version of an inverter is not supported or the device combination is invalid. Corrective measures:
|
10265 |
The device with serial number X has not been available for X day(s) (10265) Communication with one or several inverters is no longer possible. Corrective measures:
|
10267 |
Loss of communication to one or several devices (10267) Communication with one or several inverters is no longer possible. Corrective measures:
|