Checking the PV System for Ground Faults
If the LED Inverter on the Sunny Multigate is glowing red, this may indicate a ground fault in the PV system. The electrical insulation between the PV system and ground is defective.
WARNING
Danger to life due to electric shock
In the event of a ground fault, high voltages can be present.
- No terminal of the PV module must be grounded.
- Only touch the cables of the PV modules on their insulation.
- Do not touch any parts of the framework or supports of the PV modules.
- Do not connect PV modules with ground faults to the inverter.
If the Sunny Multigate indicates a ground fault in the PV array, proceed as follows:
Procedure:
- Make sure that no terminal of the PV module is grounded.
- Use Sunny Portal or Sunny Explorer to determine which of the connected inverters has a ground fault (see user manual of the communication product at www.SMA-Solar.com).
- Disconnect the affected inverter from all voltage sources ( > Disconnecting the Inverter from Voltage Sources).
- Measure voltages with a suitable measuring device.
-
Measure the voltages between the positive terminal and the ground potential.
-
Measure the voltages between the negative terminal and the ground potential.
-
Measure the voltages between the positive and negative terminals.
If the following results are present at the same time, there is a ground fault in the PV system:
-
All measured voltages are stable.
-
The sum of the two voltages to ground potential is approximately equal to the voltage between the positive and negative terminals.
-
- In case of a ground fault, solve the problem and recommission the inverter ( > Recommissioning the Inverter).
- If there is no ground fault and the error persists, contact the SMA Service Line.