Mounting the Sunny Multigate on the Wall


Additionally required mounting material (not included in the scope of delivery):

  • Four screws suitable for the size of the brackets and for the material of the back panel mounted in the industrial enclosure. The maximum permissible height of the screw head of 6 mm (0.2 in) must not be exceeded.

Procedure:

  1. WARNING

    Danger to life due to electric shock

    If screws or conductors on the connecting terminal plate are touched, there is a risk of electric shock.

    1. To avoid contact between screw and conductor, only use screws with a maximum head height of 6 mm for mounting on the brackets.
    872509452
  2. Press the four brackets on the back side of the Sunny Multigate out from the inside.
  3. The brackets snap audibly into place.
  4. Mark the drill holes using the brackets as a template.
  5. Drill the holes.
  6. 872509836
  7. Insert screws with a maximum head height of 6 mm through the brackets and tighten. Make sure not to damage the brackets.
  8. Make sure that the Sunny Multigate is securely in place.