Adjustable Parameters


You can change the following parameters for voltage and frequency monitoring in Sunny Explorer (see also user manual of Sunny Explorer at www.SMA-Solar.com).

Name

Value/range

Default value

Voltage monitoring median maximum threshold (Overvoltage/Fast)

240 V to 270 V

270.0 V

Voltage monitoring lower maximum threshold (Overvoltage/Slow)

240 V to 270 V

264.0 V

Voltage monitoring upper minimum threshold (Undervoltage/Slow)

120 V to 240 V

211.2 V

Voltage monitoring of median minimum threshold (Undervoltage/Fast)

120 V to 240 V

120.0 V

Voltage monitoring median max. threshold trip.time (Overvoltage/Fast, maximum time)

0.1 s to 2.5 s

0.16 s

Voltage monitoring lower max. threshold trip. time (Overvoltage/Slow, maximum time)

0.1 s to 5.0 s

1.0 s

Voltage monitoring upper min. threshold trip. time (Undervoltage/Slow, maximum time)

0.1 s to 5.0 s

2.0 s

Voltage monitoring median min. threshold trip.time (Undervoltage/Fast, maximum time)

0.1 s to 2.5 s

0.16 s

Frequency monitoring lower maximum threshold (Overfrequency)

50.0 Hz to 63.0 Hz

60.5 Hz

Frequency monitoring upper minimum threshold (Underfrequency)

45.0 Hz to 60.0 Hz

59.3 Hz

Frequency monitoring median minimum threshold (Underfrequency fast)

45.0 Hz to 60.0 Hz

57.0 Hz

Frq. monitoring lower max. threshold trip. time (Overfrequency, maximum time)

0.1 s to 90.0 s

0.16 s

Frq. monitoring upper min. threshold trip. time (Underfrequency, maximum time)

0.1 s to 300.0 s

0.16 s

Frequency monitoring median min. threshold trip. time (Underfrequency fast, maximum time)

0.1 s to 2.5 s

0.16 s

Limits of Accuracy for Adjustable Voltage and Frequency Trip Limit Settings

Name

Default Value

Limits of accuracy of voltage measurement

1.2%

Limits of accuracy of frequency measurement

0.05 Hz / 0.1%

Limits of accuracy of time measurement at nominal trip time

0.1%