Disconnecting the Sunny Multigate from Voltage Sources


DANGER

Risk of electric shock due to contact with live components when opening the Sunny Multigate

There are live components inside the Sunny Multigate. There is a risk of electric shock if you open the Sunny Multigate.

  1. Never open the Sunny Multigate.

Before working on the Sunny Multigate, always disconnect it from all voltage sources as described in this section.

Procedure:

  1. DANGER

    Danger to life due to electric shock

    1. Disconnect the two-pole circuit breaker and secure against reconnection.
  2. Ensure that no voltage is present at the AC terminal Grid between conductor L1 and the grounding conductor. Use a suitable measuring device.
  3. Ensure that no voltage is present at the AC terminal Grid between conductor L2 and the grounding conductor. Use a suitable measuring device.
  4. Ensure that no voltage is present at the AC terminal Inverter between conductor L1 and the grounding conductor. Use a suitable measuring device.
  5. Ensure that no voltage is present at the AC terminal Inverter between conductor L2 and the grounding conductor. Use a suitable measuring device.