Event Messages
Event number | Message, cause and corrective measures |
---|---|
1302 | Line conductor(s) or neutral conductor not connected One or more line conductors or the neutral conductor is not connected correctly. Corrective measures:
|
3701 | Residual current A DC residual current has been detected between EV Charger and vehicle. Corrective measures:
|
6112 | Watchdog reset 1 task has not triggered the software watchdog. Corrective measures:
|
6202 | Self-diagnosis > DI converter error The external component DI converter reports an error. Corrective measures:
|
6501 | Self-diagnosis > The internal temperature exceeds a permissible maximum value The product has switched off because the internal temperature is above the maximum permissible value. Corrective measures:
|
6630 | Overcurrent at point of interconnection, fast stop triggered An overcurrent has been detected at the connection point. This triggered a fast stop. |
7001 | The temperature sensor for the indoor temperature is defective. The measurement is permanently outside the measuring range limits. Corrective measures:
|
7312 | Update completed |
7320 | The device was successfully updated The firmware update was completed successfully. |
7321 | Error during transfer of firmware update with version number ##. Procedure aborted. The firmware update was not successful. Corrective measures:
|
7329 | Condition test successful The testing of the update conditions was successful. The firmware update package is suitable for this product. |
7330 | Condition test failed The testing of the update conditions was not successful. The firmware update package is not suitable for this product. Corrective measures:
|
7605 | Communication error in inverter bridge The product has detected an internal communication error. Corrective measures:
|
7619 | Communication fault with meter unit The product is not receiving any data from the external energy meter. Corrective measures:
|
7637 | Communication to internal energy meter disturbed The product has detected a communication error of internal energy meter. Corrective measures:
|
7702 | Relay defect Grid relay of the product is defective. Corrective measures:
|
8705 | Invalid spec. for |##| from |##| An invalid specification for reactive or active power has been set by the analog inputs, the digital inputs or Modbus. Corrective measures:
|
9026 | Fast stop An overcurrent has been detected at the connection point. This triggered a fast stop. |
9801 | Vehicle not compatible The vehicle is not suited for use with the EV Charger. Corrective measures:
|
9802 | Vehicle reports charging error The vehicle has detected an error during the charging mode. Corrective measures:
|
9803 | Communication between charging station and vehicle interrupted No communication can be established between EV Charger and vehicle. |
9804 | Charging station switches to charging mode [##] The charging mode was changed to the displayed mode. |
9805 | Charging mode was interrupted by vehicle. The vehicle has interrupted the charging process. Corrective measures:
|
10002 | Restart The product is performing a restart. |
10005 | System start A system start is carried out. |
10100 | Parameter [##] set successfully. [##] to [##] The displayed parameter was successfully changed. |
10101 | Setting of parameter |##| failed. [##] to [##] The displayed parameter was not changed. Corrective measures:
|
10107 | Update failed The update was not carried out successfully. Corrective measures:
|
10109 | Time adjusted / new time A new time was captured. |
10111 | Update to version ## successful The firmware update was completed successfully. |
10114 | The device has been reset to default settings. The configuration of the product has been reset to the default settings. |
10207 | New device [##] registered The displayed product was included in the system of the communication product. |
10222 | Parameter change for parameter # was initiated by user # via EVC##-#AC-10 from value # to #. Parameter change was initiated. |
10270 | Communication with the Sunny Home Manager is interrupted No communication connection to the Sunny Home Manager can be established. Corrective measures:
|
10283 | Wi-Fi module faulty The Wi-Fi module integrated in the product is defective. Corrective measures:
|
10284 | No Wi-Fi connection possible The product does not currently have a Wi-Fi connection to the selected network. Corrective measures:
|
10285 | Wi-Fi connection established |
10286 | Wi-Fi connection lost The product has lost Wi-Fi connection to the selected network. Corrective measures:
|
10294 | Access point activated The access point is active. A Wi-Fi connection can be established. |
10295 | Access point is deactivated The access point is not active. No Wi-Fi connection could be established. |
10297 | Device [##] has been deleted from [##] The displayed product has been deleted by a user from the system of the communication product. |
10321 | The device cannot be accessed at present. The device may be switched off. |
10507 | New active power limitation The product has received a new specification for active power limitation. |
10603 | Invalid configuration for the grid-supply meter |
10612 | The administrator account has been reset |
27201 | Search for update completed successfully |
27204 | Download of an update started |
27205 | Update download successful |
27206 | Download of an update not completed successfully The download of an update has failed. Corrective measures:
|
27208 | The firmware update with the version number [##] for device type [##] is being transferred. The transfer can take several minutes. |
27313 | Update started |