Connecting Additional Grounding


Qualified person

If additional grounding or equipotential bonding is required locally, you can connect additional grounding to the product. This prevents touch current if the grounding conductor at the terminal for the AC cable fails.

Additionally required material (not included in the scope of delivery):

  • 1 clamping bracket M5

  • 1 hexagon socket cap head screw M5 x 16

  • 1 washer M5

  • 1 spring washer M5

Cable requirements:

Use of fine-stranded conductors

You can use an inflexible or a flexible, fine-stranded conductor.

  1. When using a fine-stranded conductor, it has to be double crimped by a ring terminal lug. Make sure that no insulated conductor is visible when pulling or bending. This will ensure sufficient strain relief by means of the ring terminal lug.
  • Grounding cable cross-section: max. 10 mm²

Procedure:

  1. Strip off 12 mm of the grounding cable insulation.
  2. Insert the screw through the spring lock washer, the clamping bracket and the washer.
  3. Lightly screw the screw into the thread of the connection point for the additional grounding.
  4. 7726385036
  5. Guide the grounding cable between the washer and clamping bracket and tighten the screw (TX25) (torque: 6 Nm).