Event 6107
Qualified person
Event message:
Execution (State machine)
Interference device / DevFlt
Self-diagnosis / SlfDiag
Explanation:
The event message indicates an error in the program sequence of the inverter. The set time defined in the software for an operating state has been exceeded. The red LED on the inverter lights up and the inverter discontinues feed-in.
Corrective measures:
If the event message occurs briefly during starting in the morning or briefly before disconnection in the eventing, no further measures are required. In this case, the cause is voltage supply instability due to low radiation conditions.
If the event message occurs after a parameter change, ensure that the parameter settings are correct.
If the event message is permanently present, disconnect the inverter from the voltage source and then restart it.
If the event message persists after the restart, the assembly or inverter needs to be replaced.