Event 9034
Qualified person
Event message:
Error in the rapid shutdown system
Explanation:
This message can have the following causes:
The rapid shutdown function was not correctly configured.
The PV module could not be correctly disconnected. Voltage can be applied to the DC inputs of the inverter.
The standby voltage of all PV module switches of a string is > 30 V.
With DC lines laid in parallel, another inverter in the system has caused the Sunspec signal to be overwritten.
Corrective measures:
Check the settings of the rapid shutdown function and ensure that the operating mode selected is selected according to the DC disconnection unit used.
Check the functionality of the PV module switches.
Check the standby voltage of the PV module switches used and ensure that the standby voltage of all PV module switches of a string < 30 V.