Requirements on DC Conductors


  • Conductor cross-section: 3.31 mm² to 5.26 mm² (12 AWG to 10 AWG)

  • Conductor type: copper wire

  • Maximum permissible temperature: 90°C (194°F)

  • The conductors with regards to its ampacity, rated temperatures, operating conditions and its power loss must be made in accordance with the local standards and the National Electrical Code® ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1.