Event 6406
Qualified person
Event message:
Self-diagnosis
Interference device
Explanation:
The inverter has detected that the current at input A has exceeded the maximum values as laid down in the technical specifications.
Corrective measures:
If the event message occurs once or rarely, no further measures are required.
In the inverter event memory, check whether event message 3801/3802 is additionally displayed.
If the event message is displayed frequently, ensure that the PV modules have been correctly rated and wired using Sunny Design.
Ensure that the technical data for the DC input of the inverter is observed.
Ensure that the DC connection is correctly executed. Possible error sources: DC plug connections, DC cabling, PV modules.
If the event message persists despite successful checks, the assembly or inverter needs to be replaced.